Fieldbus control with embedded fieldbus
264
The following tables describe the Status Word content for the DCU profile.
DCU Profile Status Word (par. 0303)
Bit
Name
Value
Status
0
READY
1
Drive is ready to receive start command.
0
Drive is not ready.
1
ENABLED
1
External Run Enable signal received.
0
No external Run Enable signal received.
2
STARTED
1
Drive has received start command.
0
Drive has not received start command.
3
RUNNING
1
Drive is modulating.
0
Drive is not modulating.
4
ZERO_SPEED
1
Drive is at zero speed.
0
Drive has not reached zero speed.
5 ACCELERATE
1
Drive
is
accelerating.
0
Drive is not accelerating.
6
DECELERATE
1
Drive is decelerating.
0
Drive is not decelerating.
7
AT_SETPOINT
1
Drive is at setpoint. Actual value equals reference value (i.e. is
within tolerance limits).
0
Drive has not reached setpoint.
8
LIMIT
1
Operation is limited by group
settings.
0
Operation is within group
settings.
9
SUPERVISION
1
A supervised parameter (group
) is outside its
limits.
0
All supervised parameters are within limits.
10
REV_REF
1
Drive reference is in reverse direction.
0
Drive reference is in forward direction.
11
REV_ACT
1
Drive is running in reverse direction.
0
Drive is running in forward direction.
12
PANEL_LOCAL
1
Control is in control panel (or PC tool) local mode.
0
Control is not in control panel local mode.
13
FIELDBUS_LOCAL 1
Control is in fieldbus local mode
0
Control is not in fieldbus local mode.
14
EXT2_ACT
1
Control is in EXT2 mode.
0
Control is in EXT1 mode.
15
FAULT
1
Drive is in a fault state.
0
Drive is not in a fault state.
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......