Actual signals and parameters
155
4011
INTERNAL SETPNT
Selects a constant value as process PID controller reference,
when parameter 4010 SET POINT SEL value is set to
INTERNAL.
40
4012
SETPOINT MIN
Defines the minimum value for the selected PID reference signal
source.
0
4013
SETPOINT MAX
Defines the maximum value for the selected PID reference
signal source.
100
4014
FBK SEL
Selects the process actual value (feedback signal) for the
process PID controller.
ACT1
4015
FBK MULTIPLIER
Defines an extra multiplier for the value defined by parameter
4014 FBK SEL.
0
4016
ACT1 INPUT
Defines the source for actual value 1 (ACT1).
AI2
4017
ACT2 INPUT
Defines the source for actual value ACT2.
AI2
4018
ACT1 MINIMUM
Sets the minimum value for ACT1.
0
4019
ACT1 MAXIMUM
Defines the maximum value for the variable ACT1 if an analog
input is selected as a source for ACT1.
100
4020
ACT2 MINIMUM
See parameter 4018 ACT1 MINIMUM.
0
4021
ACT2 MAXIMUM
See parameter 4019 ACT1 MAXIMUM.
100
4022
SLEEP SELECTION
Activates the sleep function and selects the source for the
activation input.
NOT SEL
4023
PID SLEEP LEVEL
Defines the start limit for the sleep function.
0
4024
PID SLEEP DELAY
Defines the delay for the sleep start function.
60
4025
WAKE-UP DEV
Defines the wake-up deviation for the sleep function.
0
4026
WAKE-UP DELAY
Defines the wake-up delay for the sleep function.
0.5
4027
PID 1 PARAM SET
Defines the source from which the drive reads the signal that
selects between PID parameter set 1 and 2.
SET1
41
PROCESS PID SET 2
Process PID (PID1) control parameter set 2.
4101
GAIN
See parameter 4001 GAIN.
4102
INTEGRATION TIME
See parameter 4002 INTEGRATION TIME.
4103
DERIVATION TIME
See parameter 4003 DERIVATION TIME.
4104
PID DERIV FILTER
See parameter 4004 PID DERIV FILTER.
4105
ERROR VALUE INV
See parameter 4005 ERROR VALUE INV.
4106
UNITS
See parameter 4006 UNITS.
4107
UNIT SCALE
See parameter 4007 UNIT SCALE.
4108
0% VALUE
See parameter 4008 0% VALUE.
4109
100% VALUE
See parameter 4009 100% VALUE.
4110
SET POINT SEL
See parameter 4010 SET POINT SEL.
4111
INTERNAL SETPNT
See parameter 4011 INTERNAL SETPNT.
4112
SETPOINT MIN
See parameter 4012 SETPOINT MIN.
4113
SETPOINT MAX
See parameter 4013 SETPOINT MAX.
4114
FBK SEL
See parameter 4014 FBK SEL.
4115
FBK MULTIPLIER
See parameter 4015 FBK MULTIPLIER.
4116
ACT1 INPUT
See parameter 4016 ACT1 INPUT.
4117
ACT2 INPUT
See parameter 4017 ACT2 INPUT.
4118
ACT1 MINIMUM
See parameter 4018 ACT1 MINIMUM.
4119
ACT1 MAXIMUM
See parameter 4018 ACT1 MAXIMUM.
4120
ACT2 MINIMUM
See parameter 4020 ACT2 MINIMUM.
4121
ACT2 MAXIMUM
See parameter 4021 ACT2 MAXIMUM.
4122
SLEEP SELECTION
See parameter 4022 SLEEP SELECTION.
4123
PID SLEEP LEVEL
See parameter 4023 PID SLEEP LEVEL.
4124
PID SLEEP DELAY
See parameter 4024 PID SLEEP DELAY.
4125
WAKE-UP DEV
See parameter 4025 WAKE-UP DEV.
4126
WAKE-UP DELAY
See parameter 4026 WAKE-UP DELAY.
Parameters – short form list
Index
Name/Selection
Description
Def
Custom
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......