Actual signals and parameters
229
8403
SEQ PROG PAUSE
Selects the source for the sequence programming pause signal. When
sequence programming pause is activated all timers and outputs (RO/TO/
AO) are freezed. Sequence programming state transition is possible only by
parameter
SEQ ST FORCE.
NOT SEL
DI1(INV)
Pause signal through inverted digital input DI1. 0 = active, 1 = inactive.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
NOT SEL
No pause signal
0
DI1
Pause signal through digital input DI1. 1 = active, 0 = inactive.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
PAUSED
Sequence programming pause enabled
6
8404
SEQ PROG RESET
Selects the source for the sequence programming reset signal. Sequence
programming state (
SEQ PROG STATE) is set to the first state and all
timers and outputs (RO/TO/AO) are set to zero.
Reset is possible only when sequence programming is stopped.
NOT SEL
DI1(INV)
Reset through inverted digital input DI1. 0 = active, 1 = inactive.
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
NOT SEL
No reset signal
0
DI1
Reset through digital input DI1. 1 = active, 0 = inactive.
1
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
RESET
Reset. After reset parameter value is automatically set to NOT SEL.
6
8405
SEQ ST FORCE
Forces the sequence programming to a selected state.
Note:
State is changed only when sequence programming is paused by
SEQ PROG PAUSE and this parameter is set to the selected
state.
STATE1
STATE 1
State is forced to state 1.
1
STATE 2
State is forced to state 2.
2
STATE 3
State is forced to state 3.
3
STATE 4
State is forced to state 4.
4
STATE 5
State is forced to state 5.
5
STATE 6
State is forced to state 6.
6
STATE 7
State is forced to state 7.
7
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......