Program features
133
Counter
Drive start and stop can be controlled with counter functions. The counter function
can also be used as state change trigger signal in sequence programming. See
section
on page
.
Settings
Diagnostics
Sequence programming
The drive can be programmed to perform a sequence where the drive shifts typically
through 1 to 8 states. User defines the operation rules for the whole sequence and
for each state. The rules of a particular state are effective when the sequence
program is active and the program has entered the state. The rules to be defined for
each state are:
• Run, stop and direction commands for the drive (forward/reverse/stop)
• Acceleration and deceleration ramp time for the drive
• Source for the drive reference value
• State duration
• RO/DO/AO status
• Signal source for triggering the shift to next state
• Signal source for triggering the shift to any state (1...8).
Every state can also activate drive outputs to give an indication to external devices.
Sequence programming allows state transitions either to the next state or to a
selected state. State change can be activated with e.g. timed functions, digital inputs
and supervision functions.
Sequence programming can be applied in simple mixer applications as well as in
more complicated traverse applications.
The programming can be done with control panel or with a PC tool. ACS350 is
supported by version 2.50 (or later version) of the DriveWindow Light PC tool which
includes a graphical Sequence Programming Tool.
Parameter
Additional information
,
Start/Stop signal sources
Counter for start and stop
,
/
8435, 8436
/..../
8495
,
8496
Counter signal as state change trigger in sequence programming
Actual value
Additional information
Start/stop control pulse count
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......