Actual signals and parameters
213
3623
BOOSTER TIME
Defines the time inside which the booster is deactivated after the booster
activation signal is switched off.
00:00:00
00:00:00…23:59:58
hours:minutes:seconds
Example: If parameter 3622 BOOSTER SEL is set to DI1 and 3623
BOOSTER TIME is set to 01:30:00, the booster is active for 1 hour and 30
minutes after digital input DI is deactivated.
3626
TIMED FUNC 1 SRC
Selects the time periods for TIMED FUNC 1 SCR. Timed function can
consists of 0...4 time periods and a booster.
NOT SEL
NOT SEL
No time periods selected
0
T1
Time period 1
1
T2
Time period 2
2
T1+T2
Time periods 1 and 2
3
T3
Time period 3
4
T1+T3
Time periods 1 and 3
5
T2+T3
Time periods 2 and 3
6
T1+T2+T3
Time periods 1, 2 and 3
7
T4
Time period 4
8
T1+T4
Time periods 1 and 4
9
T2+T4
Time periods 2 and 4
10
T1+T2+T4
Time periods 1, 2 and 4
11
T3+T4
Time periods 4 and 3
12
T1+T3+T4
Time periods 1, 3 and 4
13
T2+T3+T4
Time periods 2, 3 and 4
14
T1+T2+T3+T4
Time periods 1, 2, 3 and 4
15
BOOSTER
Booster
16
T1+B
Booster and time period 1
17
T2+B
Booster and time period 2
18
T1+T2+B
Booster and time periods 1 and 2
19
T3+B
Booster and time period 3
20
T1+T3+B
Booster and time periods 1 and 3
21
T2+T3+B
Booster and time periods 2 and 3
22
T1+T2+T3+B
Booster and time periods 1, 2 and 3
23
T4+B
Booster and time period 4
24
T1+T4+B
Booster and time periods 1 and 4
25
T2+T4+B
Booster and time periods 2 and 4
26
T1+T2+T4+B
Booster and time periods 1, 2 and 4
27
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Booster active
DI
Booster time
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......