Fault tracing
280
0017
UNDERLOAD
(FF6A)
bit 0
...
)
Motor load is too low due to e.g.
release mechanism in driven
equipment.
Check for problem in driven equipment.
Check fault function parameters.
Check motor power against unit power.
0018
THERM FAIL
(5210)
bit 1
Drive internal fault. Thermistor
used for drive internal
temperature measurement is
open or short-circuited.
Contact your local ABB representative.
0021
CURR MEAS
(2211)
bit 4
Drive internal fault. Current
measurement is out of range.
Contact your local ABB representative.
0022
SUPPLY PHASE
(3130)
bit 5
(programmable
fault function
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or blown
fuse.
Trip occurs when DC voltage
ripple exceeds 14% of nominal
DC voltage.
Check input power line fuses.
Check for input power supply imbalance.
Check fault function parameters.
0023
ENCODER ERR
(7301)
bit 6
(programmable
fault function
Communication fault between
pulse encoder and pulse
encoder interface module or
between module and drive.
Check pulse encoder and its wiring, pulse encoder
interface module and its wiring and parameter group
settings.
0024
OVERSPEED
(7310)
bit 7
Motor is turning faster than
highest allowed speed due to
incorrectly set minimum/
maximum speed, insufficient
braking torque or changes in
load when using torque
reference.
Operating range limits are set
by parameters
MINIMUM
SPEED and
MAXIMUM
SPEED (with vector control) or
MINIMUM FREQ and
MAXIMUM FREQ (with
scalar control).
Check minimum/maximum speed settings.
Check adequacy of motor braking torque.
Check applicability of torque control.
Check need for brake chopper and resistor(s).
0026
DRIVE ID
(5400)
bit 9
Internal drive ID fault
Contact your local ABB representative.
0027
CONFIG FILE
(630F)
bit 10
Internal configuration file error
Contact your local ABB representative.
CODE
FAULT
CAUSE
WHAT TO DO
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......