Actual signals and parameters
180
20 LIMITS
Drive operation limits.
Speed values are used with vector control and frequency values are used
with scalar control. The control mode is selected by parameter
MOTOR
CTRL MODE.
2001
MINIMUM SPEED
Defines the allowed minimum speed.
A positive (or zero) minimum speed value defines two ranges, one positive
and one negative.
A negative minimum speed value defines one speed range.
0
-30000…30000 rpm
Minimum speed
1 = 1 rpm
2002
MAXIMUM SPEED
Defines the allowed maximum speed. See parameter
MINIMUM
SPEED.
Eur: 1500 /
US: 1800
0…30000 rpm
Maximum speed
1 = 1 rpm
2003
MAX CURRENT
Defines the allowed maximum motor current.
1.8 ·
I
2N
0.0…1.8 ·
I
2N
A
Current
1 = 0.1 A
2005
OVERVOLT CTRL
Activates or deactivates the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise to the
overvoltage control limit. To prevent the DC voltage from exceeding the limit,
the overvoltage controller automatically decreases the braking torque.
Note:
If a brake chopper and resistor are connected to the drive, the
controller must be off (selection DISABLE) to allow chopper operation.
ENABLE
DISABLE
Overvoltage control deactivated
0
ENABLE
Overvoltage control activated
1
2006
UNDERVOLT CTRL
Activates or deactivates the undervoltage control of the intermediate DC link.
If the DC voltage drops due to input power cut off, the undervoltage controller
will automatically decrease the motor speed in order to keep the voltage
above the lower limit. By decreasing the motor speed, the inertia of the load
will cause regeneration back into the drive, keeping the DC link charged and
preventing an undervoltage trip until the motor coasts to stop. This will act as
a power-loss ride-through functionality in systems with a high inertia, such as
a centrifuge or a fan. See section
on page
.
ENABLE
(TIME)
DISABLE
Undervoltage control deactivated
0
ENABLE(TIME)
Undervoltage control activated. The undervoltage control is active for
500 ms.
1
ENABLE
Undervoltage control activated. No operation time limit.
2
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
2001
2002
Speed
-(2001)
-(2002)
2002
2001
Allowed speed range
Allowed speed range
Allowed speed range
t
Speed
t
2001 value is > 0
0
0
2001 value is < 0
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......