Fault tracing
278
Fault messages generated by the drive
CODE
FAULT
CAUSE
WHAT TO DO
0001
OVERCURRENT
(2310)
bit 0
Output current has exceeded
trip level.
Check motor load.
Check acceleration time (
).
Check motor and motor cable (including phasing).
Check ambient conditions. Load capacity decreases
if installation site ambient temperature exceeds
40°C. See section
0002
DC OVERVOLT
(3210)
bit 1
Excessive intermediate circuit
DC voltage. DC overvoltage trip
limit is 420 V for 200 V drives
and 840 V for 400 V drives.
Check that overvoltage controller is on (parameter
OVERVOLT CTRL).
Check input power line for static or transient
overvoltage.
Check brake chopper and resistor (if used). DC
overvoltage control must be deactivated when brake
chopper and resistor is used.
Check deceleration time (
,
Retrofit frequency converter with brake chopper and
brake resistor.
0003
DEV OVERTEMP
(4210)
bit 2
Drive IGBT temperature is
excessive. Fault trip limit is
135°C.
Check ambient conditions. See also section
on page
.
Check air flow and fan operation.
Check motor power against unit power.
0004
SHORT CIRC
(2340)
bit 3
Short circuit in motor cable(s) or
motor
Check motor and motor cable.
0006
DC UNDERVOLT
(3220)
bit 5
Intermediate circuit DC voltage
is not sufficient due to missing
input power line phase, blown
fuse, rectifier bridge internal
fault or too low input power.
Check that undervoltage controller is on (parameter
UNDERVOLT CTRL).
Check input power supply and fuses.
0007
AI1 LOSS
(8110)
bit 6
(programmable fault
function
Analog input AI1 signal has
fallen below limit defined by
parameter
AI1 FAULT
LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
0008
AI2 LOSS
(8110)
bit 7
(programmable fault
function
Analog input AI2 signal has
fallen below limit defined by
parameter
AI2 FAULT
LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......