Actual signals and parameters
201
LAST SPEED
Protection is active. The drive generates alarm IO COMM and freezes the
speed to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
WARNING
! Make sure that it is safe to continue operation in case of
a communication break.
3
3019
COMM FAULT TIME
Defines the time delay for the fieldbus communication break supervision. See
parameter
COMM FAULT FUNC.
3
0.0...60.0 s
Delay time
1 = 0.1 s
3021
AI1 FAULT LIMIT
Defines a fault level for analog input AI1. If parameter
AI<MIN
FUNCTION is set to FAULT, the drive trips on fault AI1 LOSS, when the
analog input signal falls below the set level.
Do not set this limit below the level defined by parameter
MINIMUM
AI1.
0
0.0…100.0%
Value in percent of the full signal range
1 = 0.1%
3022
AI2 FAULT LIMIT
Defines a fault level for analog input AI2. If parameter
AI<MIN
FUNCTION is set to FAULT, the drive trips on fault AI2 LOSS, when the
analog input signal falls below the set level.
Do not set this limit below the level defined by parameter
MINIMUM
AI2.
0
0.0…100.0%
Value in percent of the full signal range
1 = 0.1%
3023
WIRING FAULT
Selects how the drive reacts when incorrect input power and motor cable
connection is detected (i.e. the input power cable is connected to the motor
connection of the drive).
Note:
Changing this parameter setting is not recommended in normal use.
The protection is to be disabled only with corner-grounded delta power
systems and very long cables.
ENABLE
DISABLE
No action
0
ENABLE
The drive trips on fault OUTP WIRING.
1
31 AUTOMATIC RESET
Automatic fault reset. Automatic resets are possible only for certain fault
types and when the automatic reset function is activated for that fault type.
3101
NR OF TRIALS
Defines the number of automatic fault resets the drive performs within the
time defined by parameter
TRIAL TIME.
If the number of automatic resets exceeds the set number (within the trial
time), the drive prevents additional automatic resets and remains stopped.
The drive must be reset from control panel or from a source selected by
parameter
Example:
Three faults have occurred during the trial time defined by
parameter
. Last fault is reset only if the number defined by parameter
3101
is 3 or more.
0
0…5
Number of the automatic resets
1 = 1
3102
TRIAL TIME
Defines the time for the automatic fault reset function. See parameter
NR OF TRIALS.
30
1.0…600.0 s
Time
1 = 0.1 s
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
X
X X
t
Trial time
x = Automatic reset
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......