Fault tracing
274
Alarm messages generated by the drive
CODE
ALARM
CAUSE
WHAT TO DO
2001
OVERCURRENT
(2310)
bit 0
(programmable fault
function
Output current limit
controller is active.
Check motor load.
Check acceleration time (
and
Check motor and motor cable (including phasing).
Check ambient conditions. Load capacity decreases if
installation site ambient temperature exceeds 40°C. See
section
.
2002
OVERVOLTAGE
(3210)
bit 1
(programmable fault
function
DC overvoltage controller
is active.
Check deceleration time (
).
Check input power line for static or transient overvoltage.
2003
UNDERVOLTAGE
(3220)
bit 2
(programmable fault
function
DC undervoltage controller
is active.
Check input power supply.
2004
DIRLOCK
bit 3
Change of direction is not
allowed.
DIRECTION settings.
2005
IO COMM
(7510)
bit 4
(programmable fault
function
Fieldbus communication
break
Check status of fieldbus communication. See chapter
Fieldbus control with fieldbus adapter
or appropriate fieldbus adapter manual.
Check fault function parameter settings.
Check connections.
Check if master can communicate.
2006
AI1 LOSS
(8110)
bit 5
(programmable fault
function
Analog input AI1 signal has
fallen below limit defined by
parameter
AI1 FAULT
LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
2007
AI2 LOSS
(8110)
bit 6
(programmable fault
function
Analog input AI2 signal has
fallen below limit defined by
parameter
AI2 FAULT
LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
2008
PANEL LOSS
(5300)
bit 7
(programmable
fault function
)
Control panel selected as
active control location for
drive has ceased
communicating.
Check panel connection.
Check fault function parameters.
Check control panel connector.
Refit control panel in mounting platform.
If drive is external control mode (REM) and is set to accept
start/stop, direction commands or references via control
panel:
Check group
and
settings.
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......