Actual signals and parameters
144
0133
PID 2 DEVIATION
Deviation of the PID2 controller, i.e. the difference between the reference
value and the actual value. Unit depends on parameter
UNIT and
UNIT SCALE settings.
-
0134
COMM RO WORD
Relay output Control Word through fieldbus (decimal). See parameter
RELAY OUTPUT 1.
1 = 1
0135
COMM VALUE 1
Data received from fieldbus
1 = 1
0136
COMM VALUE 2
Data received from fieldbus
1 = 1
0137
PROCESS VAR 1
Process variable 1 defined by parameter group
-
0138
PROCESS VAR 2
Process variable 2 defined by parameter group
-
0139
PROCESS VAR 3
Process variable 3 defined by parameter group
-
0140
RUN TIME
Elapsed time counter (thousands of hours). Runs when the drive is
running. Counter cannot be reset.
1 = 0.01 kh
0141
MWH COUNTER
MWH counter. Counter cannot be reset.
1 = 1 MWh
0142
REVOLUTION CNTR
Motor revolution counter (millions of revolutions). The counter can be
reset by pressing UP and DOWN buttons simultaneously when the
control panel is in Parameter mode.
1 = 1 Mrev
0143
DRIVE ON TIME HI
Drive control board power-on time in days. Counter cannot be reset.
1 = 1 days
0144
DRIVE ON TIME LO
Drive control board power-on time in 2 second ticks (30 ticks = 60
seconds). Counter cannot be reset.
0145
MOTOR TEMP
Measured motor temperature. Unit depends on the sensor type selected
by group
parameters.
1 = 1
0146
MECH ANGLE
Calculated mechanical angle
1 = 1
0147
MECH REVS
Mechanical revolutions, i.e. the motor shaft revolutions calculated by the
encoder
1 = 1
0148
Z PLS DETECTED
Encoder zero pulse detector. 0 = not detected, 1 = detected.
1 = 1
0158
PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2)
1 = 1
0159
PID COMM VALUE 2
Data received from fieldbus for PID control (PID1 and PID2)
1 = 1
0160
DI 1-5 STATUS
Status of digital inputs. Example: 10000 = DI1 is on, DI2...DI5 are off.
0161
PULSE INPUT FREQ
Value of frequency input in Hz
1 = 1 Hz
0162
RO STATUS
Status of relay output. 1 = RO is energised, 0 = RO is de-energized.
1 = 1
0163
TO STATUS
Status of transistor output, when transistor output is used as a digital
output.
1 = 1
0164
TO FREQUENCY
Transistor output frequency, when transistor output is used as a
frequency output.
1 = 1 Hz
0165
TIMER VALUE
Timer value of timed start/stop. See parameter group
.
1 = 0.01 s
0166
COUNTER VALUE
Pulse counter value of counter start/stop. See parameter group
1 = 1
0167
SEQ PROG STS
Status Word of the sequence programming:
Bit 0 = ENABLED (1 = enabled)
Bit 1 = STARTED
Bit 2 = PAUSED
Bit 3 = LOGIC VALUE (logic operation defined by parameters
…
).
1 = 1
0168
SEQ PROG STATE
Active state of the sequence programming. 1...8 = state 1...8.
1 = 1
Actual signals
No.
Name/Value
Description
FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......