Actual signals and parameters
210
PTC
The function is active. The temperature is supervised using PTC sensor.
Analog output AO feeds constant current through the sensor. The resistance
of the sensor increases sharply as the motor temperature rises over the PTC
reference temperature (Tref), as does the voltage over the resistor. The
temperature measurement function reads the voltage through analog input
AI1/2 and converts it into ohms. The figure below shows typical PTC sensor
resistance values as a function of the motor operating temperature.
4
THERM(0)
The function is active. Motor temperature is monitored using a PTC sensor
(see selection PTC) connected to drive via a normally closed thermistor relay
connected to a digital input. 0 = motor overtemperature.
5
THERM(1)
The function is active. Motor temperature is monitored using a PTC sensor
(see selection PTC) connected to drive via a normally open thermistor relay
connected to a digital input. 1 = motor overtemperature.
6
3502
INPUT SELECTION
Selects the source for the motor temperature measurement signal.
AI1
AI1
Analog input AI1. Used when PT100 or PTC sensor is selected for the
temperature measurement.
1
AI2
Analog input AI2. Used when PT100 or PTC sensor is selected for the
temperature measurement
2
DI1
Digital input DI1. Used when par.
SENSOR TYPE value is set to
THERMI(0)/(1).
3
DI2
Digital input DI2. Used when par.
SENSOR TYPE value is set to
THERMI(0)/(1).
4
DI3
Digital input DI3. Used when par.
SENSOR TYPE value is set to
THERMI(0)/(1).
5
DI4
Digital input DI4. Used when par.
SENSOR TYPE value is set to
THERMI(0)/(1).
6
DI5
Digital input DI5. Used when par.
SENSOR TYPE value is set to
THERMI(0)/(1).
7
3503
ALARM LIMIT
Defines the alarm limit for motor temperature measurement. Alarm MOTOR
TEMP indication is given when the limit is exceeded. When par.
SENSOR TYPE value is set to THERMI(0)/(1): 1 = alarm.
0
x…x
Alarm limit
-
3504
FAULT LIMIT
Defines the fault trip limit for motor temperature measurement. The drive trips
on fault MOT OVERTEMP when the limit is exceeded. When par.
SENSOR TYPE value is set to THERMI(0)/(1): 1 = fault.
0
x…x
Fault limit
-
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
100
550
1330
4000
ohm
T
Temperature
Resistance
Normal
0 … 1.5 kohm
Excessive
> 4 kohm
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......