Actual signals and parameters
216
4008
0% VALUE
Defines together with parameter
100% VALUE the scaling applied to
the PID controller’s actual values.
0
x…x
Unit and range depend on the unit and scale defined by parameters
UNITS
and
UNIT SCALE.
4009
100% VALUE
Defines together with parameter
0% VALUE the scaling applied to the
PID controller’s actual values.
100
x...x
Unit and range depend on the unit and scale defined by parameters
UNITS
and
UNIT SCALE.
4010
SET POINT SEL
Selects the source for the process PID controller reference signal.
AI1
KEYPAD
Control panel
0
AI1
Analog input AI1
1
AI2
Analog input AI2
2
COMM
Fieldbus reference REF2
8
COMM+AI1
Summation of fieldbus reference REF2 and analog input AI1. See section
Reference selection and correction
on page
9
COMM*AI1
Multiplication of fieldbus reference REF2 and analog input AI1. See section
Reference selection and correction
on page
10
DI3U,4D(RNC)
Digital input 3: Reference increase. Digital input DI4: Reference decrease.
Stop command resets the reference to zero. The reference is not saved if the
control source is changed from EXT1 to EXT2, from EXT2 to EXT1 or from
LOC to REM.
11
DI3U,4D(NC)
Digital input 3: Reference increase. Digital input DI4: Reference decrease.
The program stores the active reference (not reset by a stop command). The
reference is not saved if the control source is changed from EXT1 to EXT2,
from EXT2 to EXT1 or from LOC to REM.
12
AI1+AI2
Reference is calculated with the following equation:
REF = AI1(%) + AI2(%) - 50%
14
AI1*AI2
Reference is calculated with the following equation:
REF = AI(%) · (AI2(%) / 50%)
15
AI1-AI2
Reference is calculated with the following equation:
REF = AI1(%) + 50% - AI2(%)
16
AI1/AI2
Reference is calculated with the following equation:
REF = AI1(%) · (50% / AI2 (%))
17
INTERNAL
A constant value defined by parameter
INTERNAL SETPNT
19
DI4U,5D(NC)
See selection DI3U,4D(NC).
31
FREQ INPUT
Frequency input
32
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Internal scale
(%)
4009
4008
100%
0%
Units
(4006)
Scale
(4007)
-1000%
+1000%
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......