Actual signals and parameters
209
3413
OUTPUT2 MIN
Sets the minimum display value for the signal selected by parameter
SIGNAL2 PARAM. See par.
SIGNAL1 MIN.
-
x…x
Setting range depends on parameter
setting.
-
3414
OUTPUT2 MAX
Sets the maximum display value for the signal selected by parameter
SIGNAL2 PARAM. See par.
SIGNAL1 MIN.
-
x…x
Setting range depends on parameter
setting.
-
3415
SIGNAL3 PARAM
Selects the third signal to be displayed on the control panel in display mode.
See par
SIGNAL1 PARAM.
105
0, 101…172
Parameter index in group
If value is set to 0, no signal is selected.
1 = 1
3416
SIGNAL3 MIN
Defines the minimum value for the signal selected by parameter
. See
par.
SIGNAL1 MIN.
-
x…x
Setting range depends on parameter
SIGNAL 3 PARAM setting.
-
3417
SIGNAL3 MAX
Defines the maximum value for the signal selected by parameter
SIGNAL3 PARAM. See par.
SIGNAL1 MIN.
-
x…x
Setting range depends on parameter
SIGNAL3 PARAM setting.
-
3418
OUTPUT3 DSP
FORM
Defines the format for the displayed signal selected by par.
SIGNAL3
PARAM.
DIRECT
OUTPUT1 DSP FORM.
-
3419
OUTPUT3 UNIT
Selects the unit for the for the displayed signal selected by parameter
SIGNAL3 PARAM.
-
OUTPUT1 UNIT.
-
3420
OUTPUT3 MIN
Sets the minimum display value for the signal selected by parameter
SIGNAL3 PARAM. See par.
SIGNAL1 MIN.
-
x…x
Setting range depends on parameter
SIGNAL3 PARAM setting.
-
3421
OUTPUT3 MAX
Sets the maximum display value for the signal selected by parameter
SIGNAL3 PARAM
.
See par.
SIGNAL1 MIN.
-
x…x
Setting range depends on parameter
setting.
-
35 MOTOR TEMP
MEAS
Motor temperature measurement. See section
measurement through the standard I/O
.
3501
SENSOR TYPE
Activates the motor temperature measurement function and selects the
sensor type. See also parameter group
.
NONE
NONE
The function is inactive.
0
1 x PT100
The function is active. The temperature is measured with one Pt 100 sensor.
Analog output AO feeds constant current through the sensor. The sensor
resistance increases as the motor temperature rises, as does the voltage
over the sensor. The temperature measurement function reads the voltage
through analog input AI1/2 and converts it to degrees centigrade.
1
2 x PT100
The function is active. Temperature is measured using two Pt 100 sensors.
See selection 1 x PT100.
2
3 x PT100
The function is active. Temperature is measured using three Pt 100 sensors.
See selection 1 x PT100.
3
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......