Program features
128
State shifts
Settings
Parameter
Additional information
/
Mechanical brake activation through RO/DO
Zero speed delay
Group
Brake function settings
RFG INPUT
TO ZERO
CLOSE
BRAKE
OPEN
BRAKE
From any state
1/1/1
0/1/1
1/1/0
1/1/0
1)
2)
RELEASE RFG
INPUT
3)
4)
7)
8)
5)
NO
MODULATION
0/0/1
9)
6)
A
A
State (Symbol
)
- NN: State name
- X/Y/Z: State outputs/operations
X = 1
Open the brake. The relay output set to brake on/off control energises.
Y = 1
Forced start. The function keeps the internal Start on until the brake is closed in spite of the
status of the external Start signal.
Z = 1
Ramp in zero. Forces the used speed reference (internal) to zero along a ramp.
NN
X/Y/Z
State change conditions (Symbol
)
1)
Brake control active 0 -> 1 OR Inverter is modulating = 0
2)
Motor magnetised = 1 AND Drive running = 1
3)
Brake is open AND Brake open delay passed AND Start = 1
4)
Start = 0
5)
Start = 0
6)
Start = 1
7)
Actual motor speed < Brake close speed AND Start = 0
8)
Start = 1
9)
Brake is closed AND Brake close delay passed = 1 AND Start = 0
RFG = Ramp Function
Generator in the speed
control loop (reference
handling).
(rising edge)
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......