Actual signals and parameters
224
4306
RUNTIME FREQ LVL
Defines the brake close speed. When frequency falls below the set level
during run, the brake is closed. The brake is re-opened when the
requirements set by parameters
...
are met.
0
0.0…100.0%
Value in percent of the maximum frequency (with scalar control) or the
maximum speed (with vector control). If parameter value is set to zero, the
function is disabled. The control mode is selected by parameter
MOTOR CTRL MODE.
1 = 0.1%
50 ENCODER
Encoder connection.
For more information, see
MTAC-01 Pulse Encoder Interface Module User’s
Manual
[3AFE68591091 (English)].
5001
PULSE NR
States the number of encoder pulses per one revolution.
1024
32...16384 ppr
Pulse number in pulses per round (ppr)
1 = 1
5002
ENCODER ENABLE
Enables the encoder.
DISABLE
DISABLE
Disabled
0
ENABLE
Enabled
1
5003
ENCODER FAULT
Defines the operation of the drive if a failure is detected in communication
between the pulse encoder and the pulse encoder interface module, or
between the module and the drive.
FAULT
FAULT
The drive trips on fault ENCODER ERR.
1
ALARM
The drive generates alarm ENCODER ERROR.
2
5010
Z PLS ENABLE
Enables the encoder zero (Z) pulse. Zero pulse is used for position reset.
DISABLE
DISABLE
Disabled
0
ENABLE
Enabled
1
5011
POSITION RESET
Enables the position reset.
DISABLE
DISABLE
Disabled
0
ENABLE
Enabled
1
51 EXT COMM
MODULE
The parameters need to be adjusted only when a fieldbus adapter module
(optional) is installed and activated by parameter
COMM PROT SEL.
For more details on the parameters, refer to the manual of the fieldbus
module and chapter
Fieldbus control with fieldbus adapter
. These parameter
settings will remain the same even though the macro is changed.
Note:
In adapter module the parameter group number is 1.
5101
FBA TYPE
Displays the type of the connected fieldbus adapter module.
NOT DEFINED
Fieldbus module is not found, or it is not properly connected, or parameter
COMM PROT SEL setting is not EXT FBA.
0
PROFIBUS-DP
Profibus adapter module
1
CANopen
CANopen adapter module
32
DEVICENET
DeviceNet adapter module
37
5102
FB PAR 2
These parameters are adapter module-specific. For more information, see
the module manual. Note that not all of these parameters are necessarily
visible.
...
....
5126
FB PAR 26
5127
FBA PAR REFRESH
Validates any changed adapter module configuration parameter settings.
After refreshing, the value reverts automatically to DONE.
DONE
Refreshing done
0
REFRESH
Refreshing
1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......