Application macros
86
Summary of I/O connections of application macros
The following table gives the summary of the default I/O connections of all
application macros.
Input/output
Macro
ABB
Standard
3-wire
Alternate
Motor
Potentiom.
Hand/Auto
PID Control
Torque
Control
AI1
(0…10 V)
Freq. ref.
Speed ref.
Speed ref.
-
Speed ref.
(Hand)
Speed ref.
(Hand) / Proc.
ref. (PID)
Speed ref.
(Speed)
AI2
(0…20 mA)
-
-
-
-
Speed ref.
(Auto)
Process value Torque ref.
(Torque)
AO
Output freq.
Speed
Speed
Speed
Speed
Speed
Speed
DI1
Stop/Start
Start (pulse)
Start (fwd)
Stop/Start
Stop/Start
(Hand)
Stop/Start
(Hand)
Stop/Start
(Speed)
DI2
Fwd/Rev
Stop (pulse)
Start (rev)
Fwd/Rev
Fwd/Rev
(Hand)
Hand/PID
Fwd/Rev
DI3
Const. speed
input 1
Fwd/Rev
Const. speed
input 1
Speed ref. up Hand/Auto
Const.
speed 1
Speed/Torque
DI4
Const. speed
input 2
Const. speed
input 1
Const. speed
input 2
Speed ref.
down
Fwd/Rev
(Auto)
Run enable
Const.
speed 1
DI5
Ramp pair
selection
Const. speed
input 2
Ramp pair
selection
Const.
speed 1
Stop/Start
(Auto)
Stop/Start
(PID)
Ramp pair
selection
RO
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
DO
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Fault (-1)
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......