Program features
107
Power loss ride-through
If the incoming supply voltage is cut off, the drive will continue to operate by utilising
the kinetic energy of the rotating motor. The drive will be fully operational as long as
the motor rotates and generates energy to the drive. The drive can continue the
operation after the break if the main contactor remained closed.
Settings
Parameter
UNDERVOLT CTRL
DC Magnetising
When DC Magnetising is activated, the drive automatically magnetises the motor
before starting. This feature guarantees the highest possible breakaway torque, up
to 180% of motor nominal torque. By adjusting the premagnetising time, it is possible
to synchronise the motor start and e.g. a mechanical brake release. The Automatic
Start feature and DC Magnetising cannot be activated at the same time.
Settings
Parameters
START FUNCTION and
DC MAGN TIME
Maintenance trigger
A maintenance trigger can be activated to show a notice on the panel display when
e.g. drive power consumption has exceeded the defined trigger point.
Settings
Parameter group
130
260
390
520
1.6
4.8
8
11.2
14.4
t
(s)
U
DC
f
out
T
M
U
DC
= Intermediate circuit voltage of the drive,
f
out
= output frequency of the drive,
T
M
= Motor torque
Loss of supply voltage at nominal load (f
out
= 40 Hz). The intermediate circuit DC voltage drops to the
minimum limit. The controller keeps the voltage steady as long as the input power is switched off. The
drive runs the motor in generator mode. The motor speed falls but the drive is operational as long as
the motor has enough kinetic energy.
U
input power
20
40
60
80
40
80
120
160
T
M
(N·m)
f
out
(Hz)
U
DC
(Vdc)
0
0
0
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......