Actual signals and parameters
202
3103
DELAY TIME
Defines the time that the drive will wait after a fault before attempting an
automatic reset. See parameter
NR OF TRIALS. If delay time is set to
zero, the drive resets immediately.
0
0.0…120.0 s
Time
1 = 0.1 s
3104
AR OVERCURRENT
Activates/deactivates the automatic reset for the overcurrent fault.
Automatically resets the fault (OVERCURRENT) after the delay set by par.
DELAY TIME.
DISABLE
DISABLE
Inactive
0
ENABLE
Active
1
3105
AR OVERVOLTAGE
Activates/deactivates the automatic reset for the intermediate link
overvoltage fault. Automatically resets the fault (DC OVERVOLT) after the
delay set by par.
DELAY TIME.
DISABLE
DISABLE
Inactive
0
ENABLE
Active
1
3106
AR UNDERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
undervoltage fault. Automatically resets the fault (DC UNDERVOLTAGE)
after the delay set by par.
DELAY TIME.
DISABLE
DISABLE
Inactive
0
ENABLE
Active
1
3107
AR AI<MIN
Activates/deactivates the automatic reset for fault AI<MIN (analog input
signal under the allowed minimum level). Automatically resets the fault after
the delay set by par.
DELAY TIME.
DISABLE
DISABLE
Inactive
0
ENABLE
Active
WARNING!
The drive may restart even after a long stop if the
analog input signal is restored. Ensure that the use of this feature
will not cause danger.
1
3108
AR EXTERNAL FLT
Activates/deactivates the automatic reset for the EXTERNAL FAULT 1/2.
Automatically resets the fault after the delay set by par.
DELAY TIME.
DISABLE
DISABLE
Inactive
0
ENABLE
Active
1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......