Actual signals and parameters
182
DI2
See selection DI1.
2
DI3
See selection DI1.
3
DI4
See selection DI1.
4
DI5
See selection DI1.
5
COMM
Fieldbus interface as the source for the torque limit 1/2 selection, i.e. control
word
FB CMD WORD 1 bit 15. The control word is sent by the fieldbus
controller via the fieldbus adapter or embedded fieldbus (modbus) to the
drive. For the control word bits, see section
on
page
.
Maximum torque limit 1 is defined by parameter
MAX TORQUE 1 and
maximum torque limit 2 is defined by parameter
MAX TORQUE 2.
Note:
This setting applies only for the DCU profile!
7
DI1(INV)
Inverted digital input DI1. 1 = parameter
MAX TORQUE 1 value.
0 = parameter
-1
DI2(INV)
See selection DI1(INV).
-2
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
2015
MIN TORQUE 1
Defines minimum torque limit 1 for the drive. See parameter
MIN
TORQUE SEL.
-300
-600.0…0.0%
Value in percent of the motor nominal torque
1 = 0.1%
2016
MIN TORQUE 2
Defines minimum torque limit 2 for the drive. See parameter
MIN
TORQUE SEL.
-300
-600.0…0.0%
Value in percent of the motor nominal torque
1 = 0.1%
2017
MAX TORQUE 1
Defines maximum torque limit 1 for the drive. See parameter
MAX
TORQUE SEL.
300
0.0…600.0%
Value in percent of the motor nominal torque
1 = 0.1%
2018
MAX TORQUE 2
Defines maximum torque limit 2 for the drive. See parameter
MAX
TORQUE SEL.
300
0.0…600.0%
Value in percent of the motor nominal torque
1 = 0.1%
2019
BRAKE CHOPPER
Old parameter. Left out in sw version 2.51b and later. See parameter
.
2020
BRAKE CHOPPER
Selects the brake chopper control. (Only in sw version 2.51b or later).
INBUILT
INBUILT
Internal brake chopper control.
Note:
Ensure the brake resistor(s) is installed and the overvoltage control is
switched off by setting parameter
OVERVOLT CTRL to selection
DISABLE.
0
EXTERNAL
External brake chopper control.
Note:
The drive is compatible only with ABB
ACS-BRK-X
brake units.
Note:
Ensure the brake unit is installed and the overvoltage control is
switched off by setting parameter
OVERVOLT CTRL to selection
DISABLE.
1
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......