Actual signals and parameters
167
1209
TIMED MODE SEL
Selects timed function activated speed into use when parameter
CONST SPEED SEL selection is TIMED FUN1&2.
CS1/2/3/4
EXT/CS1/2/3
External speed reference or constant speed selection with TIMED FUNC 1
and TIMED FUNC 2. 1 = timed function active, 0 = timed function inactive.
1
CS1/2/3/4
Constant speed selection with TIMED FUNC 1 and TIMED FUNC 2.
1 = timed function active, 0 = timed function inactive.
2
13 ANALOGUE INPUTS
Analog input signal processing
1301
MINIMUM AI1
Defines the minimum %-value that corresponds to minimum mA/(V) signal for
analog input AI1. When used as a reference, the value corresponds to the
reference minimum setting.
0...20 mA 0...100%
4...20 mA 20...100%
-10...10 mA -50...50%
Example:
If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter
REF1 MIN.
Note:
MINIMUM AI value must not exceed MAXIMUM AI value.
1%
-100.0…100.0%
Value in percent of the full signal range. Example: If the minimum value for
analog input is 4 mA, the percent value for 0…20 mA range is:
(4 mA / 20 mA) · 100% = 20%
1 = 0.1%
1302
MAXIMUM AI1
Defines the maximum %-value that corresponds to maximum mA/(V) signal
for analog input AI1. When used as a reference, the value corresponds to the
reference maximum setting.
0...20 mA 0...100%
4...20 mA 20...100%
-10...10 mA -50...50%
Example:
If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter
REF1 MAX.
100
-100.0…100.0%
Value in percent of the full signal range. Example: If the maximum value for
analog input is 10 mA, the percent value for 0…20 mA range is:
(10 mA / 20 mA) · 100% = 50%
1 = 0.1%
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
TIMED
FUNC 1
TIMED
FUNC 2
Operation
0
0
External reference
1
0
Speed defined by parameter
CONST SPEED 1
0
1
Speed defined by parameter
CONST SPEED 2
1
1
Speed defined by parameter
CONST SPEED 3
TIMED
FUNC 1
TIMED
FUNC 2
Operation
0
0
Speed defined by parameter
CONST SPEED 1
1
0
Speed defined by parameter
CONST SPEED 2
0
1
Speed defined by parameter
CONST SPEED 3
1
1
Speed defined by parameter
CONST SPEED 4
=
=
=
=
=
=
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......