Actual signals and parameters
187
DI3(INV)
See selection DI1(INV).
-3
DI4(INV)
See selection DI1(INV).
-4
DI5(INV)
See selection DI1(INV).
-5
2202
ACCELER TIME 1
Defines the acceleration time 1 i.e. the time required for the speed to change
from zero to the speed defined by parameter
MAXIMUM FREQ (with
scalar control) /
MAXIMUM SPEED (with vector control). The control
mode is selected by parameter
MOTOR CTRL MODE.
- If the speed reference increases faster than the set acceleration rate, the
motor speed will follow the acceleration rate.
- If the speed reference increases slower than the set acceleration rate, the
motor speed will follow the reference signal.
- If the acceleration time is set too short, the drive will automatically prolong
the acceleration in order not to exceed the drive operating limits.
Actual acceleration time depends on parameter
RAMP SHAPE 1
setting.
5
0.0…1800.0 s
Time
1 = 0.1 s
2203
DECELER TIME 1
Defines the deceleration time 1 i.e. the time required for the speed to change
from the value defined by parameter
MAXIMUM FREQ (with scalar
control) /
MAXIMUM SPEED (with vector control)
to zero. The control
mode is selected by parameter
MOTOR CTRL MODE.
- If the speed reference decreases slower than the set deceleration rate, the
motor speed will follow the reference signal.
- If the reference changes faster than the set deceleration rate, the motor
speed will follow the deceleration rate.
- If the deceleration time is set too short, the drive will automatically prolong
the deceleration in order not to exceed drive operating limits.
If a short deceleration time is needed for a high inertia application, the drive
should be equipped with a brake resistor.
Actual deceleration time depends on parameter
RAMP SHAPE 1
setting.
5
0.0…1800.0 s
Time
1 = 0.1 s
Parameters – complete descriptions
Index Name/Selection
Description
Def, FbEq
Summary of Contents for ACS350 Series
Page 1: ...ACS350 User s Manual ACS350 Drives 0 37 22 kW 0 5 30 HP ...
Page 4: ......
Page 8: ...Safety 8 ...
Page 18: ...Table of contents 18 ...
Page 24: ...Hardware description 24 ...
Page 44: ...Installation checklist 44 ...
Page 56: ...Start up control with I O and ID Run 56 ...
Page 140: ...Program features 140 ...
Page 242: ...Actual signals and parameters 242 ...
Page 266: ...Fieldbus control with embedded fieldbus 266 ...
Page 284: ...Fault tracing 284 ...
Page 288: ...Maintenance and hardware diagnostics 288 ...
Page 309: ...Dimensions 309 Frame size R2 IP20 NEMA 1 3AFE68586658 A Frame size R2 IP20 NEMA 1 VAR EMC ...
Page 311: ...Dimensions 311 Frame size R3 IP20 NEMA 1 3AFE68579872 B Frame size R3 IP20 NEMA 1 VAR EMC ...
Page 313: ......