Section 11
General function block features
11.1
Definite time characteristics
11.1.1
Definite time operation
The DT mode is enabled when the
Operating curve type
setting is selected either as "ANSI
Def. Time" or "IEC Def. Time". In the DT mode, the
TRIP
output of the function is
activated when the time calculation exceeds the set
Trip delay time
.
The user can determine the reset in the DT mode with the
Reset delay time
setting, which
provides the delayed reset property when needed.
Figure 334:
Operation of the counter in drop-off
In case 1, the reset is delayed with the
Reset delay time
setting and in case 2, the counter
is reset immediately, because the
Reset delay time
setting is set to zero.
The
Type of reset curve
setting has no effect on the reset method when the
DT mode is selected, but the reset is determined solely with the
Reset delay
time
setting.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......