1MAC050144-MB C
Section 8
Measurement functions
615 series ANSI
549
Technical Manual
8.3.4
Settings
Table 454: I1, I2, I0 Non group settings
Parameter
Values (Range) Unit Step Default
Description
Operation
1=Enable
5=Disable
1=Enable
Operation Off / On
Ps Seq A Hi high Lim
0.00...40.00
xIn
1.40
High alarm current limit for positive sequence current
Ps Seq A high limit
0.00...40.00
xIn
1.20
High warning current limit for positive sequence current
Ps Seq A low limit
0.00...40.00
xIn
0.00
Low warning current limit for positive sequence current
Ps Seq A low low Lim
0.00...40.00
xIn
0.00
Low alarm current limit for positive sequence current
Ps Seq A deadband
100...100000
2500
Deadband configuration value for positive sequence current for integral
calculation. (percentage of difference between min and max as 0,001 %
s)
Ng Seq A Hi high Lim
0.00...40.00
xIn
0.20
High alarm current limit for negative sequence current
Ng Seq A High limit
0.00...40.00
xIn
0.05
High warning current limit for negative sequence current
Ng Seq A low limit
0.00...40.00
xIn
0.00
Low warning current limit for negative sequence current
Ng Seq A low low Lim
0.00...40.00
xIn
0.00
Low alarm current limit for negative sequence current
Ng Seq A deadband
100...100000
2500
Deadband configuration value for negative sequence current for integral
calculation. (percentage of difference between min and max as 0,001 %
s)
Zro A Hi high Lim
0.00...40.00
xIn
0.20
High alarm current limit for zero sequence current
Zro A High limit
0.00...40.00
xIn
0.05
High warning current limit for zero sequence current
Zro A low limit
0.00...40.00
xIn
0.00
Low warning current limit for zero sequence current
Zro A low low Lim
0.00...40.00
xIn
0.00
Low alarm current limit for zero sequence current
Zro A deadband
100...100000
2500
Deadband configuration value for zero sequence current for integral
calculation. (percentage of difference between min and max as 0,001 %
s)
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......