1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
375
Technical Manual
Figure 178:
Operating characteristics of the restrained ground-fault protection
function
Figure 179:
Setting range of the operating characteristics for the restrained
differential current principle of the ground-fault protection function
The
Trip value
setting is used for defining the characteristics of the function. The
differential current value required for tripping is constant at the stabilizing current values
0.0 < IB/In < 1.0, where In is the nominal current, and the In in this context refers to the
nominal of the phase current inputs. When the stabilizing current is higher than 1.0, the
slope of the operation characteristic (ID/IB) is constant at 50 percent. Different operating
characteristics are possible based on the
Trip value
setting.
To calculate the directional differential current ID_COSPHI, the fundamental frequency
amplitude of both the residual and neutral currents has to be above 4 percent of In. If
neither or only one condition is fulfilled at a time, the cos
φ
term is forced to 1. After the
conditions are fulfilled, both currents must stay above 2 percent of In to allow the
continuous calculation of the cos
φ
term.
0.0
0.5
1.0
1.5
0.0
1.0
2.0
3.0
IB/In
ID_COSPHI/ In
ID
IB
TRIPPING
NON TRIPPING
Trip value
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......