![background image](http://html.mh-extra.com/html/abb/615-series-ansi/615-series-ansi_technical-manual_4665077.webp)
Section 3
1MAC050144-MB C
Basic functions
70
615 series ANSI
Technical Manual
Figure 8:
Binary input filtering
1
t
0
2
t
1
3
Input signal
4
Filtered input signal
5
Filter time
At the beginning, the input signal is at the high state, the short low state is filtered and no
input state change is detected. The low state starting from the time t
0
exceeds the filter
time, which means that the change in the input state is detected and the time tag attached
to the input change is t
0
. The high state starting from t
1
is detected and the time tag t
1
is
attached.
Each binary input has a filter time parameter
Input # filter
, where # is the number of the
binary input of the module in question (for example
Input 1 filter
).
Table 42:
Input filter parameter values
3.8.2
Binary input inversion
The parameter
Input # invert
is used to invert a binary input.
Table 43:
Binary input states
When a binary input is inverted, the state of the input is TRUE (1) when no control voltage
is applied to its terminals. Accordingly, the input state is FALSE (0) when a control
voltage is applied to the terminals of the binary input.
Parameter
Values
Default
Input # filter time
5...1000 ms
5 ms
1
2
3
4
5
5
Control voltage
Input # invert
State of binary input
No
0
False (0)
Yes
0
True (1)
No
1
True (0)
Yes
1
False (0)
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......