1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
97
Technical Manual
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status information.
Respectively, T_POS_OK is used to validate the intermediate or faulty breaker position.
Table 76:
Cross reference between circuit breaker position and the output of the function block
Function block
Figure 35:
Function blocks
Settings
The function does not have any parameters available in LHMI or Protection and Control
IED Manager (PCM600).
3.13.2
Minimum pulse timer
3.13.2.1
Minimum pulse timer TP
Identification
Function block
Figure 36:
Function block
Functionality
The Minimum pulse timer function TP block contains two independent timers
running in
milliseconds
. The function has a settable pulse length (in milliseconds). The timers are
used for setting the minimum pulse length for example, the signal outputs. Once the input
is activated the function gives out a pulse (Cold load time setting). But if the input remains
Circuit breaker position
Output of the function block
T_POS_CL
T_POS_OP
T_POS_OK
Intermediate '00'
FALSE
FALSE
FALSE
Close '01'
TRUE
FALSE
TRUE
Open '10'
FALSE
TRUE
TRUE
Faulty '11'
TRUE
TRUE
FALSE
T_POS_CL
POS
T_POS_OP
POS
T_POS_OK
POS
CLOSE
OPEN
OK
Functional description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum pulse timer
TPGAPC
TPGAPC
TP
TP
IN2
IN1
OUT1
OUT2
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......