1MAC050144-MB C
Section 5
Protection related functions
615 series ANSI
403
Technical Manual
5.5.2
Function block
Figure 203:
Function block
5.5.3
Functionality
The arc flash detector AFD detects arc situations in air insulated metal-clad switchgears
caused by, for example, human errors during maintenance or insulation breakdown during
operation.
The function detects light from an arc either locally or via a remote light signal. The
function also monitors phase and ground currents to be able to make accurate decisions on
ongoing arcing situations.
The function contains a blocking functionality. Blocking deactivates all outputs and resets
timers.
5.5.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable.
The operation of the arc flash detector can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
Figure 204:
Functional module diagram. I_A, I_B and I_C represent phase currents.
Level detector 1
The measured phase currents are compared phase-wise with the set
Phase pickup value
. If
the measured value exceeds the set
Phase pickup value
, the level detector reports the
exceeding of the value to the operation mode selector.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......