Section 7
1MAC050144-MB C
Control functions
528
615 series ANSI
Technical Manual
7.3.7
Settings
Table 432: 25 group settings
Table 433: 25 non-group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Live dead mode
-1=Off
1=Both Dead
Energizing check mode
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
Difference voltage
0.01...0.50
xVn
0.01
0.05
Maximum voltage difference limit
Difference frequency
0.001...0.100
xFn
0
0.001
Maximum frequency difference limit
Difference angle
5...90
deg
1
5
Maximum angle difference limit
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
1=enable
Operation Off / On
5=disable
Synchro check mode
1=Off
2=Synchronous
Synchro check operation mode
2=Synchronous
3=Asynchronous
Control mode
1=Continuous
1=Continuous
Selection of synchro check command or Continuous control
mode
2=Command
Dead line value
0.1...0.8
xVn
0.1
0.2
Voltage low limit line for energizing check
Live line value
0.2...1.0
xVn
0.1
0.5
Voltage high limit line for energizing check
Dead bus value
0.1...0.8
xVn
0.1
0.2
Voltage low limit bus for energizing check
Live bus value
0.2...1.0
xVn
0.1
0.5
Voltage high limit bus for energizing check
Close pulse
200...60000
ms
10
200
Breaker closing pulse duration
Max energizing V
0.50...1.15
xVn
0.01
1.05
Maximum voltage for energizing
Phase shift
-180...180
deg
1
180
Correction of phase difference between measured U_BUS and
U_LINE
Minimum Syn time
0...60000
ms
10
0
Minimum time to accept synchronizing
Maximum Syn time
100...6000000
ms
10
2000
Maximum time to accept synchronizing
Energizing time
100...60000
ms
10
100
Time delay for energizing check
Closing time of CB
40...250
ms
10
60
Closing time of the breaker
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......