The pickup value multiplication is normally done when the inrush detection function
(INR) is connected to the
ENA_MULT
input.
Timer
Once activated, the timer activates the
PICKUP
output. Depending on the value of the
Operating curve type
setting, the time characteristics are according to DT or IDMT. When
the operation timer has reached the value of
Trip delay time
in the DT mode or the
maximum value defined by the inverse time curve, the
TRIP
output is activated.
When the user programmable IDMT curve is selected, the operate time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation happens, that is, a fault suddenly disappears before the trip delay is
exceeded, the timer reset state is activated. The functionality of the timer in the reset state
depends on the combination of the
Operating curve type
,
Type of reset curve
and
Reset
delay time
settings. When the DT characteristic is selected, the reset timer runs until the
set
Reset delay time
value is exceeded. When the IDMT curves are selected, the
Type of
reset curve
setting can be set to "Immediate", "Def time reset" or "Inverse reset". The reset
curve type "Immediate" causes an immediate reset. With the reset curve type "Def time
reset", the reset time depends on the
Reset delay time
setting. With the reset curve type
"Inverse reset", the reset time depends on the current during the drop-off situation. If the
drop-off situation continues, the reset timer is reset and the
PICKUP
output is deactivated.
The setting
Time multiplier
is used for scaling the IDMT trip and reset times.
The setting parameter
Minimum trip time
defines the minimum desired trip time for IDMT.
The setting is applicable only when the IDMT curves are used.
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the
percentual ratio of the pickup situation and the set trip time. The value is available through
the Monitored data view.
Do not set the multiplier setting
Pickup value Mult
higher than necessary.
If the value is too high, the function may not trip at all during an inrush
followed by a fault, no matter how severe the fault is.
The "Inverse reset" selection is only supported with ANSI or user
programmable types of the IDMT operating curves. If another operating
curve type is selected, an immediate reset occurs during the drop-off
situation.
The
Minimum trip time
setting should be used with great care because the
operation time is according to the IDMT curve, but always at least the value
of the
Minimum operate time
setting. For more information, see the
General function block features section in this manual
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......