Section 7
Control functions
615 series ANSI
529
Technical Manual
7.3.8
Monitored data
Table 434: 25 monitored data
Name
Type
Values (Range)
Unit
Description
ENERG_STATE
Enum
0=Unknown
Energization state of Line and Bus
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
U_DIFF_MEAS
FLOAT32
0.00...1.00
xVn
Calculated voltage amplitude difference
FR_DIFF_MEAS
FLOAT32
0.000...0.100
xFn
Calculated voltage frequency difference
PH_DIFF_MEAS
FLOAT32
0.00...180.00
deg
Calculated voltage phase angle difference
U_DIFF_SYNC
BOOLEAN
0=False
Voltage difference out of limit for synchronizing
1=True
PH_DIF_SYNC
BOOLEAN
0=False
Phase angle difference out of limit for synchronizing
1=True
FR_DIFF_SYNC
BOOLEAN
0=False
Frequency difference out of limit for synchronizing
1=True
25
Enum
1=on
Status
2=blocked
3=test
4=test/blocked
5=off