Section 3
1MAC050144-MB C
Basic functions
96
615 series ANSI
Technical Manual
R_Trig detects the transition from FALSE to TRUE at the CLK input. When the rising
edge is detected, the element assigns the output to TRUE. At the next execution round, the
output is returned to FALSE despite the state of the input.
Function block
Figure 33:
Function block
Settings
The function does not have any parameters available in LHMI or Protection and Control
IED Manager (PCM600).
3.13.1.8
F_TRIG function block
Functionality
F_Trig is used as a falling edge detector.
The function detects the transition from TRUE to FALSE at the CLK input. When the
falling edge is detected, the element assigns the Q output to TRUE. At the next execution
round, the output is returned to FALSE despite the state of the input.
Function block
Figure 34:
Function block
Settings
The function does not have any parameters available in LHMI or Protection and Control
IED Manager (PCM600).
3.13.1.9
T_POS_XX function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is fed to
the POS input.
R_TRIG
CLK
O
F_TRIG
CLK
O
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......