1MAC050144-MB C
Section 7
Control functions
615 series ANSI
499
Technical Manual
• "AR inoperative": the
PROT_CRD
output is active, if the AR function is disabled or
in the lockout state, or if the
INHIBIT_RECL
input is active
• "CB close manual": the
PROT_CRD
output is active for the reclaim time if the circuit
breaker has been manually closed, that is, the AR function has not issued a close
command
• "AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
• "always": the
PROT_CRD
output is constantly active
Figure 271:
Configuration example of using the
PROT_CRD
output for protection
blocking
If the
Protection crd limit
setting has the value "1", the instantaneous three-phase
overcurrent protection function 50P-3 is disabled or blocked after the first shot.
7.2.4.7
Circuit breaker controller
Circuit breaker controller contains two features: SOTF and frequent-operation counter.
SOTF protects the AR function in permanent faults.
The circuit breaker position information is controlled with the
CB closed Pos status
setting. The setting value "TRUE” means that when the circuit breaker is closed, the
CB_POS
input is TRUE. When the setting value is “FALSE”, the
CB_POS
input is
FALSE, provided that the circuit breaker is closed. The reclose command pulse time can
be controlled with the
Close pulse time
setting: the
CLOSE_CB
output is active for the time
set with the
Close pulse time
setting. The
CLOSE_CB
output is deactivated also when the
circuit breaker is detected to be closed, that is, when the
CB_POS
input changes from open
state to closed state. The
Wait close time
setting defines the time after the
CLOSE_CB
command activation, during which the circuit breaker should be closed. If the closing of
circuit breaker does not happen during this time, the autoreclose function is driven to
lockout or, if allowed, an auto-initiation is activated.
The main motivation for autoreclosing to begin with is the assumption that the fault is
temporary by nature, and that a momentary de-energizing of the power line and an
automatic reclosing restores the power supply. However, when the power line is manually
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......