1MAC050144-MB C
Section 3
Basic functions
615 series ANSI
39
Technical Manual
Section 3
Basic functions
3.1
General parameters
Table 4:
Analog input settings, phase currents
Table 5:
Analog input settings, residual currentt
Parameter
Values (Range)
Unit
Step
Default
Description
Secondary current
2=1A
3=5A
2=1A
Rated secondary current
Primary current
1.0...6000.0
A
0.1
600A
Rated primary current
Amplitude corr. A
0.900...1.100
0.001
1.000
Phase A amplitude correction factor
Amplitude corr. B
0.900...1.100
0.001
1.000
Phase B amplitude correction factor
Amplitude corr. C
0.900...1.100
0.001
1.000
Phase C amplitude correction factor
Nominal Current
39...4000
A
1
1300
Network Nominal Current (ln)
Rated Secondary Value
1.000...50.000
mV/Hz
0.001
3.000
Rated Secondary Value (RSV) ratio
Reverse polarity
0=False
1=True
0=False
Reverse the polarity of the phase CTs
Parameter
Values (Range)
Unit
Step
Default
Description
Secondary current
1=0.2A
2=1A
3=5A
2=5A
Secondary current
Primary current
1.0...6000.0
A
0.1
100.0
Primary current
Amplitude corr.
0.900...1.100
0.001
1.000
Amplitude correction
Reverse polarity
0=False
1=True
0=False
Reverse the polarity of the residual CT
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......