Section 9
1MAC050144-MB C
Recording functions
606
615 series ANSI
Technical Manual
9.1.4
Settings
Table 509: Non-group general settings for digital fault recorder
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=Enable
5=Disable
1
1=Enable
DFR Enabled /
Disabled
Record length
10...500
fundamental
cycles
1
50
Size of the
recording in
fundamental
cycles
Pre-trg length
5...95
%
1
10
Length of the
recording
preceding the
triggering
Operation
mode
1=Saturation
2=Overwrite
1
1
Operation
mode of the
recorder
Exclusion time
0...1 000 000
ms
1
0
The time
during which
triggerings of
same type are
ignored
Storage rate
32, 16, 8
samples per
fundamental
cycle
32
Storage rate of
the waveform
recording
Periodic trig
time
0...604 800
s
10
0
Time between
periodic
triggerings
Stor. mode
periodic
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for periodic
triggering
Stor. mode
manual
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for manual
triggering
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......