Section 4
1MAC050144-MB C
Protection functions
166
615 series ANSI
Technical Manual
For defining the operation sector, there are five modes available through the
Operation
mode
setting.
Table 157: Operation modes
The directional operation can be selected with the
Directional mode
setting. The user can
select either "Non-directional", "Forward" or "Reverse" operation. The operation criterion
is selected with the
Operation mode
setting. By setting
Allow Non Dir
to "True",
non-directional operation is allowed when directional information is invalid.
The
Characteristic angle
setting is used in "Phase angle" mode to adjust the operation
according to the method of neutral point grounding so that in an isolated network the
Characteristic angle
(
φ
RCA
) = -90° and in a compensated network
φ
RCA
= 0°. In addition,
the characteristic angle can be changed via the control signal
RCA_CTL
, in which case the
alternatives are -90° and 0°. The operation of
RCA_CTL
depends on the
Characteristic
angle
setting.
The
Correction angle
setting can be used to improve selectivity when there are
inaccuracies due to measurement transformers. The setting decreases the operation sector.
The correction can only be used with the "IoCos" or "IoSin" modes.
The minimum signal level which allows directional operation can be set by using the
Min
trip current
and
Min trip voltage
settings.
When polarizing quantity (residual voltage (-Uo)) is inverted because of switched voltage
measurement cables, the correction can be done by setting the
Pol reversal
to "True"
which turns polarizing quantity by 180 degrees.
The directional calculation module calculates several values which are presented in the
monitored data.
Operation mode
Description
Phase angle
The operating sectors for forward and reverse are
defined with the settings
Min forward angle
,
Max
forward angle
,
Min reverse angle
and
Max reverse
angle.
IoSin
The operating sectors are defined as "forward"
when the mathematical expression has a positive
value and "reverse" when the value is negative
IoCos
As "IoSin" mode. Only cosine is used for calculating
the operation current.
Phase angle 80
The sector maximum values are frozen to 80
degrees, respectively. Only Min forward angle and
Min reverse angle
are settable.
Phase angle 88
The sector maximum values are frozen to 88
degrees. Otherwise as "Phase angle 80" mode.
For definitions of different directional ground-fault characteristics, see the
Directional ground-fault characteristics section in this manual.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......