PRODUCT INFORMATION

VM17/VM17L - DISTRIBUTION BOARD

17 WAY

SPECIFICATIONS

Rated Operational Voltage

415V AC maximum, 50Hz

Maximum Current

100A

Rated Insulation Voltage

1000V

Short Circuit Withstand

10kA

Degree of Protection

IP40 – Indoor Use Only

Usage

Recommended for use with copper conductors only

Number of Ways (Poles)

17 Ways – 1 row of 17 Ways

Maintenance

This product does not require maintenance once 

installed

DIMENSIONS AND WEIGHT

Height

Width

Depth

Weight

Cover Assembly

323mm

402mm

35mm

2.0 kg

Base (cut out size)

277mm

355mm

93mm

1.8 kg

INSTALLER NOTES

EARTH AND NEUTRAL BUSBAR LAYOUT

Material

Number

of bars

Double 

screw 

tunnels

Single 

screw 

tunnels

Earth Bar

Brass  Steel 

1

3

12

Neutral Bar

Brass  Steel

1

2

8

RCD Neutral Bar

Brass  Steel

3

1

3

•  The VM17 is guaranteed for a period of 1 year from the date of purchase against defects in 

       workmanship and materials.

• 

Defects will be rectified by replacement of the product.

•  This warranty becomes null and void if, in our opinion, the product has been misused, incorrectly installed, 

tampered with, or subject to power surges. 

•  The warranty does not include any labour or other associated expenses that may be involved in removal or 

installation of the product.

•  To obtain a replacement under this guarantee, return the goods (prepaid) to the place of purchase          

(proof of purchase must be supplied).

WARRANTY STATEMENT

1.  This product is designed to be             

installed inside a wall cavity only (flush            

mounting). Do not surface mount.

2.  For surface mounting use VM17SK. 

Surface mount enclosure in conjunction 

with this board.

3.  The metal wall enclosure must be 

earthed.

4.  Fold out tags (x4) on the side walls of 

the enclosure can be folded out to set 

the correct height onto the studs.

5.  Door hinge pins are easily removable 

and the door can be reversed so that it 

swings either left or right.

6.  This product is designed to be used 

with New Zealand and Australia’s MEN 

system.

7.  DO NOT install a link between the 

neutral bars and earth bar on circuits 

dedicated to RCDs.

8.  Please ensure circuits and protective 

devices are adequately identified during 

installation.

INSV0035