8.14
Tap change position indication, 84T
8.14.1
Identification
8.14.2
Function block
Figure 320:
Function block
8.14.3
Functionality
The binary converter function 84T is used for converting binary-coded tap position inputs
to their decimal equivalent when a tap position indication is received from the I/O board
with the help of the coded binary inputs.
There are three user-selectable conversion modes available for the 7-bit binary inputs
where MSB is used as the SIGN bit: the natural binary-coded boolean input to the signed
integer output, binary coded decimal BCD input to the signed integer output and binary
reflected GRAY coded input to the signed integer output.
8.14.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are Enable and Disable. When the function is disabled, the tap position
quality information is changed accordingly. When the tap position information is not
available, it is recommended to disable this function with the
Operation
setting.
The operation of tap position indication function can be described by using a module
diagram. All the modules in the diagram are explained in the next sections.
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tap position
TPOSSLTC
TPOSM
84T
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......