Section 4
Protection functions
615 series ANSI
205
Technical Manual
Figure 96:
Functional module diagram
Level detector
The calculated negative-sequence current is compared to the
Pickup value
setting. If the
measured value exceeds the
Pickup value
setting, the function activates the timer module.
Timer
Once activated, the timer activates the
PICKUP
output. Depending on the value of the set
Operating curve type
, the time characteristics are according to DT or IDMT. When the
operation timer has reached the value set by
Trip delay time
in the DT mode or the
maximum value defined by the inverse time curve, the
TRIP
output is activated.
In a drop-off situation, that is, when the value of the negative-sequence current drops
below the
Pickup value
setting, the reset timer is activated and the
PICKUP
output resets
after the time delay of
Reset delay time
for the DT characteristics. For IDMT, the reset time
depends on the curve type selected.
For the IDMT curves, it is possible to define minimum and maximum trip times with the
Minimum trip time
and
Maximum trip time
settings. The
Machine time Mult
setting
parameter corresponds to the machine constant, equal to the I
2
2
t constant of the machine,
as stated by the machine manufacturer. In case there is a mismatch between the used CT
and the protected motor's nominal current values, it is possible to fit the IDMT curves for
the protected motor using the
Rated current
setting.
The activation of the
TRIP
output activates the
BLK_RESTART
output. The deactivation
of the
TRIP
output activates the cooling timer. The timer is set to the value entered in the
Cooling time
setting. The
BLK_RESTART
output is kept active until the cooling timer is
exceeded. If the negative-sequence current increases above the set value during this
period, the
TRIP
output is activated immediately.
The operation timer counting can be frozen to the prevailing value by activating the
FR_TIMER
input.
The
T_ENARESTART
output indicates the duration for which the
BLK_RESTART
output
remains active, that is, it indicates the remaining time of the cooling timer. The value is
available through the Monitored data view.
TRIP
BLK_RESTART
PICKUP
BLOCK
I
2
Level
detector
Timer
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......