Section 4
1MAC050144-MB C
Protection functions
182
615 series ANSI
Technical Manual
Figure 83:
Operating characteristic I
0
cos(φ) in reverse fault
Phase angle, classic 80
The operation criterion phase angle classic 80 is selected with the
Operation mode
setting
using the value "Phase angle 80".
Phase angle classic 80 implements the same functionality as the phase angle, but with the
following differences:
• The
Max forward angle
and
Max reverse angle
settings are not settable but have a
fixed value of 80 degrees
• The sector limits of the fixed sectors are rounded.
The sector rounding is used for cancelling the CT measurement errors at low current
amplitudes. When the current amplitude falls below three percent of the nominal current,
the sector is reduced to 70 degrees at the fixed sector side. This makes the protection more
selective, which means that the phase angle measurement errors do not cause faulty
operation.
There is no sector rounding on the other side of the sector.
If the current amplitude falls below one percent of the nominal current, the
direction enters the non-directional area.
RCA
= 0 deg
Correction
angle
Min operating
current
0
0
0
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......