For instance, if the startup time of the motor is 11 seconds and the calculated operate time
of the thermal protection stage with no prior load is 25 seconds, one motor startup uses
11/25
≈
45 percent of the thermal capacity of the motor. Therefore, the restart disable level
must be set to below 100 percent - 45 percent = 55 percent, for example to 50 percent (100
percent - (45 p margin), where margin is 5 percent).
Setting the thermal alarm level
Tripping due to high overload is avoided by reducing the load of the motor on a prior
alarm.
The value of
Alarm thermal value
is set to a level which allows the use of the full thermal
capacity of the motor without causing a trip due to a long overload time. Generally, the
prior alarm level is set to a value of 80 to 90 percent of the trip level.