![background image](http://html.mh-extra.com/html/abb/615-series-ansi/615-series-ansi_technical-manual_4665429.webp)
Section 6
1MAC050144-MB C
Supervision functions
422
615 series ANSI
Technical Manual
Figure 218:
Significance of the
Difference Cor time
setting
The
Difference Cor time
setting is used instead of the auxiliary contact to accumulate the
energy from the time the main contact opens. If the setting is positive, the calculation of
energy starts after the auxiliary contact has opened and when the delay is equal to the value
set with the
Difference Cor time
setting. When the setting is negative, the calculation starts
in advance by the correction time before the auxiliary contact opens.
The accumulated energy outputs
IPOW_A (_B, _C)
are available through the
Monitored data view on the LHMI or through tools via communications. The values can
be reset by setting the parameter
52CMx.acc.Energy
setting to true in the clear menu from
WHMI or LHMI.
Alarm limit check
The
IPOW_ALM
alarm is activated when the accumulated energy exceeds the value set
with the
Alm Acc currents Pwr
threshold setting. However, when the energy exceeds the
limit value set with the
LO Acc currents Pwr
threshold setting, the
IPOW_LO
output is
activated.
The
IPOW_ALM
and
IPOW_LO
outputs can be blocked by activating the binary input
BLOCK
.
6.1.4.6
Remaining life of the circuit breaker
Every time the breaker operates, the life of the circuit breaker reduces due to wearing. The
wearing in the breaker depends on the tripping current, and the remaining life of the
breaker is estimated from the circuit breaker trip curve provided by the manufacturer. The
remaining life is decremented at least with one when the circuit breaker is opened.
The operation of the remaining life of the circuit breaker subfunction can be described by
using a module diagram. All the modules in the diagram are explained in the next sections.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......