Section 4
1MAC050144-MB C
Protection functions
212
615 series ANSI
Technical Manual
4.1.10.6
Signals
Table 199: 46R Input signals
Table 200: 46R Output signals
4.1.10.7
Settings
Table 201: 46R Group settings
Table 202: 46R Non group settings
4.1.10.8
Monitored data
Table 203: 46R Monitored data
Name
Type
Default
Description
I2
SIGNAL
0
Negative phase sequence current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
0.05...1.00
xIn
0.01
0.75
Pickup value
Trip delay time
100...60000
ms
10
100
Trip delay time
Parameter
Values (Range)
Unit Step Default
Description
Operation
1=Enable
5=Disable
5=Disable
Operation Disable / Enable
Name
Type
Values (Range) Unit Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
46R
Enum
1=enabled
2=blocked
3=test
4=test/blocked
5=disabled
Status
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......