to follow the characteristics of the object to be protected more closely and the thermal
capacity of the object is very well known, a value between "50" and "100 percent" is
required.
For motor applications where, for example, two hot starts are allowed instead of three cold
starts, the value of the setting "
Weighting factor p
= 40 percent" has proved to be useful.
Setting the value of
Weighting factor p
significantly below "50 percent" should be handled
carefully as there is a possibility to overload the protected object as a thermal unit might
allow too many hot starts or the thermal history of the motor has not sufficiently been taken
into account.