Figure 205:
Arc flash detector with one IED
Arc flash detector with several IEDs
When using several IEDs, the IED protecting the outgoing feeder trips the circuit breaker
of the outgoing feeder when detecting an arc at the cable terminations. If the IED
protecting the outgoing feeder detects an arc on the busbar or in the breaker compartment
via one of the other lens sensors, it will generate a signal to the IED protecting the
incoming feeder. When detecting the signal, the IED protecting the incoming feeder trips
the circuit breaker of the incoming feeder and generates an external trip signal to all IEDs