1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
143
Technical Manual
Figure 63:
Phasors in a single-phase ground fault, phase A to ground, and a
two-phase short circuit, phases B-C, are short-circuited when the
polarizing quantity is the positive-sequence voltage V1
Network rotating direction
Typically, the network rotating direction is counterclockwise and defined as "ABC". If the
network rotating direction is reversed, meaning clockwise, that is, "ACB", the equations
for calculating the angle difference need to be changed. The network rotating direction is
defined with a system parameter
Phase rotation
. The change in the network rotating
direction affects the phase-to-phase voltages polarization method where the calculated
angle difference needs to be rotated 180 degrees. Also, when the sequence components are
used, which are the positive-sequence voltage or negative-sequence voltage components,
the calculation of the components is affected but the angle difference calculation remains
the same. When the phase-to-ground voltages are used as the polarizing method, the
network rotating direction change has no effect on the direction calculation.
The network rotating direction is set in the IED using the parameter in the
HMI menu:
Configuration > System > Phase rotation
. The default
parameter value is "ABC".
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......