Section 6
Supervision functions
615 series ANSI
437
Technical Manual
Figure 230:
Incorrect connection of trip-circuit monitoring
A connection of three protection IEDs with a double pole trip circuit is shown in the
following figure. Only the IED R3 has an internal TCM circuit. In order to test the
operation of the IED R2, but not to trip the circuit breaker, the upper trip contact of the IED
R2 is disconnected, as shown in the figure, while the lower contact is still connected. When
the IED R2 operates, the coil current starts to flow through the internal resistor of the IED
R3 and the resistor burns immediately. As proven with the previous examples, both trip
contacts must operate together. Attention should also be paid for correct usage of the
trip-circuit monitoring while, for example, testing the IED.