![background image](http://html.mh-extra.com/html/abb/615-series-ansi/615-series-ansi_technical-manual_4665630.webp)
1MAC050144-MB C
Section 10
Other functions
615 series ANSI
623
Technical Manual
10.5.4
Settings
Table 533: TONGAPC Non group settings
10.5.5
Technical data
Table 534: TONGAPC Technical data
Parameter
Values (Range) Unit Step Default Description
On delay time 1
0...3600000
ms
10
0
On delay time
On delay time 2
0...3600000
ms
10
0
On delay time
On delay time 3
0...3600000
ms
10
0
On delay time
On delay time 4
0...3600000
ms
10
0
On delay time
On delay time 5
0...3600000
ms
10
0
On delay time
On delay time 6
0...3600000
ms
10
0
On delay time
On delay time 7
0...3600000
ms
10
0
On delay time
On delay time 8
0...3600000
ms
10
0
On delay time
Characteristic
Value
Operate time
accuracy
±1.0% of the set
value or ±20 ms