1MAC050144-MB C
Section 4
Protection functions
615 series ANSI
225
Technical Manual
When the user-programmable IDMT curve is selected, the trip time characteristics are
defined by the parameters
Curve parameter A
,
Curve parameter B
,
Curve parameter C
,
Curve parameter D
and
Curve parameter E
.
If a drop-off situation occurs, that is, a fault suddenly disappears before the trip delay is
exceeded, the reset state is activated. The behavior in the drop-off situation depends on the
selected trip time characteristics. If the DT characteristics are selected, the reset timer runs
until the set
Reset delay time
value is exceeded. If the drop-off situation exceeds the set
Reset delay time
, the timer is reset and the
PICKUP
output is deactivated.
When the IDMT trip time curve is selected, the functionality of the timer in the drop-off
state depends on the combination of the
Type of reset curve
and
Reset delay time
settings.
Table 221: The reset time functionality when the IDMT trip time curve is selected
Type of reset curve
Description of operation
“Immediate”
The trip timer is reset instantaneously when drop-off
occurs
“Def time reset”
The trip timer is frozen during drop-off. The trip timer
is reset after the set
Reset delay time
is exceeded
“DT Lin decr rst”
The trip timer value linearly decreases during the
drop-off situation. The trip timer is reset after the set
Reset delay time
is exceeded
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......