Section 4
1MAC050144-MB C
Protection functions
168
615 series ANSI
Technical Manual
The setting parameter
Minimum trip time
defines the minimum desired trip time for IDMT.
The setting is applicable only when the IDMT curves are used.
The timer calculates the pickup duration (PICKUP_DUR) value which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available through
the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the
BLOCK
input and the global setting
"Configuration/System/
Blocking
mode
"
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the IED program. The
influence of the
BLOCK
signal activation is preselected with the global setting
Blocking
mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
trip timer is frozen to the prevailing value. In the "Block all" mode, the whole function is
blocked and the timers are reset. In the "Block TRIP output" mode, the function operates
normally but the
TRIP
output is not activated.
4.1.6.5
Directional ground-fault principles
In many cases it is difficult to achieve selective ground-fault protection based on the
magnitude of zero sequence current only. To obtain a selective ground-fault protection
scheme, it is necessary to take the phase angle of I
0
into account. This is done by
comparing the phase angle of I
0
to that of the zero sequence voltage (-V
0
).
Relay characteristic angle
The
Characteristic angle
, also known as Relay Characteristic Angle (RCA), Relay Base
Angle or Maximum Torque Angle (MTA), is used in the "Phase angle" mode to turn the
directional characteristic, if the expected fault current angle does not coincide with the
polarizing quantity to produce the maximum torque. That is, RCA is the angle between the
maximum torque line and polarizing quantity. If the polarizing quantity is in phase with
the maximum torque line, RCA is 0 degrees. The angle is positive if operating current lags
the polarizing quantity and negative if it leads the polarizing quantity.
Example 1.
The "Phase angle" mode is selected, compensated network (
φ
RCA = 0 deg)
=>
Characteristic angle
= 0 deg
The
Minimum trip time
setting should be used with great care because the
operation time is according to the IDMT curve, but always at least the value
of the
Minimum operate time
setting. For more information, see the
General function block features section in this manual.
Summary of Contents for 615 Series ANSI
Page 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Page 2: ......
Page 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Page 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Page 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Page 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Page 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Page 712: ......